Type 3254¶
This Type has two main purposes: estimating the performances from the environmental conditions and the compressor frequency, and to determine the supply air state. The capacity output can be controlled through the frequency input. Moreover, the Type 3254 is able to operate in heating and cooling mode, and to simulate defrost cycles. For more details, have a look at the in-depth features section.
Inputs¶
- 1. Inlet (return) air temperaturereal
The dry-bulb temperature of the air entering the indoor unit of the heat pump. This air is typically at room air conditions.
- 2. Inlet (return) air humidity ratioreal \(\geq 0\)
The absolute humidity ratio of the air entering the indoor unit of the heat pump. This air is typically at room air conditions.
This input is not considered if parameter 1 is set to 2.
- 3. Inlet (return) air relative humidityreal \(\in [0, 100]\)
The percent relative humidity of the air entering the indoor unit of the heat pump. This air is typically at room air conditions.
This input is not considered if parameter 1 is set to 4.
- 4. Inlet (return) air pressurereal \(\geq 0\)
The absolute pressure of the air entering the indoor unit of the heat pump. This air is typically at room air conditions.
- 5. Inlet (return) air mass flow ratereal \(\geq 0\)
The air flow rate entering the indoor unit of the heat pump.
- 6. Outdoor air dry bulb temperaturereal \(\in [0, 100]\)
The dry-bulb temperature of the air entering the outdoor unit of the heat pump.
- 7. Outdoor air humidity ratioreal \(\geq 0\)
The absolute humidity ratio of the air entering the outdoor unit of the heat pump.
- 8. Outdoor air relative humidityreal \(\in [0, 100]\)
The percent relative humidity of the air entering the outdoor unit of the heat pump.
- 9. Outdoor air pressurereal \(\geq 0\)
The absolute pressure of the air entering the outdoor unit of the heat pump.
- 10. Normalized compressor frequencyreal \(\geq 0\)
The frequency of the compressor, normalized by its rated value (parameters 7 and 8).
- 11. Indoor unit fan speed ratioreal
The indoor unit fan speed, normalized by its rated value. It is also the value of the normalized air flow rate. If negative, the return air mass flow rate input will be used instead.
- 12. Operating modeinteger \(\in \{0, 1\}\)
Setting for heating/cooling mode:
\(0\)
cooling mode
\(1\)
heating mode
- 13. Defrost modeinteger \(\in \{0, 1, 2\}\)
Setting for defrost mode:
\(0\)
Set to defrost mode
\(1\)
Set to recovery mode
\(2\)
Set to steady-state mode
- 14. Recovery penaltyreal \(\in [0, 1]\)
Correction factor for the heating capacity when the heat pump operates in recovery mode. See recovery penalty.
Parameters¶
- 1. Humidity inputs modeinteger \(\in \{2, 4\}\)
This parameter indicates which input to this model will be used for the moist air calculations:
\(2\)
Percent relative humidity (input 3)
\(4\)
Humidity ratio (input 2)
- 2. Rated total cooling powerreal \(\geq 0\)
The input power of the heat pump at its rated conditions in cooling mode.
- 3. Rated cooling capacityreal \(\geq 0\)
The cooling capacity of the heat pump at its rated conditions.
- 4. Rated total heating powerreal \(\geq 0\)
The input power of the heat pump at its rated conditions in heating mode.
- 5. Rated heating capacityreal \(\geq 0\)
The heating capacity of the heat pump at its rated conditions.
- 6. Rated inlet air flow ratereal \(\geq 0\)
The rated value of the air volumetric flow rate entering the indoor unit of the heat pump.
- 7. Rated cooling frequencyreal \(\geq 0\)
The rated frequency of the heat pump compressor when operating in cooling mode.
- 8. Rated heating frequencyreal \(\geq 0\)
The rated frequency of the heat pump compressor when operating in heating mode.
- 9. Indoor fan rated powerreal \(\geq 0\)
The rated power of the indoor unit fan.
- 10. Outdoor fan rated powerreal \(\geq 0\)
The rated power of the outdoor unit fan.
- 11. Backup heater capacityreal
The capacity of the backup heater that is used when the heat pump cannot work due to extreme conditions. If the value is negative, the same value as the heating rated capacity will be used.
- 12. Logical Unit - cooling modeinteger \(\geq 10\)
The logical unit which will be assigned to the data file which contains the heat pump cooling performance data.
- 13. Logical Unit - heating modeinteger \(\geq 10\)
The logical unit which will be assigned to the data file which contains the heat pump heating performance data.
Outputs¶
- 1. Outlet (supply) air temperaturereal
The dry-bulb temperature of the air exiting the indoor unit of the heat pump.
- 2. Outlet (supply) air humidity ratioreal \(\geq 0\)
The absolute humidity ratio of the air exiting the indoor unit of the heat pump.
- 3. Outlet (supply) air relative humidityreal \(\in [0, 100]\)
The percent relative humidity of the air exiting the indoor unit of the heat pump.
- 4. Outlet (supply) air pressurereal \(\geq 0\)
The absolute air pressure of the air exiting the indoor unit of the heat pump.
- 5. Outlet (supply) air mass flow ratereal \(\geq 0\)
The flow rate of dry air exiting the indoor unit of the heat pump.
- 6. Total cooling ratereal \(\geq 0\)
The rate at which heat (both sensible and latent) is removed from the conditioned air stream in cooling mode.
- 7. Sensible cooling ratereal \(\geq 0\)
The rate at which sensible heat is removed from the conditioned air stream in cooling mode.
- 8. Latent cooling ratereal \(\geq 0\)
The rate at which latent heat is removed from the conditioned air stream in cooling mode.
- 9. Heat rejection ratereal \(\geq 0\)
The rate at which heat is rejected to the outdoor air from the outdoor unit in cooling mode.
- 10. Total heating capacityreal \(\geq 0\)
The rate at which heat is added to the indoor unit air stream in heating mode.
- 11. Heat absorption ratereal \(\geq 0\)
The rate at which heat is absorbed from the outdoor air by the outdoor unit in heating mode.
- 12. Total power consumptionreal \(\geq 0\)
The total power input (compressor, indoor fan and outdoor fan) required to operate the heat pump.
- 13. Coefficient of performance (COP)real \(\geq 0\)
The ratio between the capacity (heating or cooling depending on the operating mode) and the total input power.
- 14. Energy efficiency rating (EER)real \(\geq 0\)
Same as the COP, but with the capacity expressed in BTU/h and the input power expressed in watts.
- 15. Indoor fan powerreal \(\geq 0\)
The rate at which the indoor unit fan is consuming energy.
- 16. Outdoor fan powerreal \(\geq 0\)
The rate at which the outdoor unit fan is consuming energy.
- 17. Compressor powerreal \(\geq 0\)
The rate at which the heat pump compressor is consuming energy.
- 18. Compressor frequencyreal \(\geq 0\)
The actual frequency of the heat pump compressor. It might be different from the one asked by the compressor if the heat pump shuts down (see output 22). It has the same units as the rated compressor frequency.
- 19. Condensate temperaturereal
The temperature of the condensate exiting the indoor unit in cooling mode.
- 20. Condensate mass flow ratereal \(\geq 0\)
The mass flow rate of the condensate exiting the indoor unit in cooling mode.
- 21. Defrost modeinteger \(\in \{0, 1, 2\}\)
The defrost mode of the heat pump.
\(0\)
Defrost mode
\(1\)
Recovery mode
\(2\)
Steady-state mode
- 22. Forced shutdown signalinteger \(\in \{0, 1\}\)
Returns \(0\) if the heat pump works noramlly, and \(1\) if it is shutdown because of an invalid set of input conditions.
Performance file¶
The Type 3254 relies on performance maps to evaluate the heat pump performance. Therefore, performance maps must be provided in the form of performance files—one for each operating mode. Those performance files must follow a specific format, detailed below. Adequately formatting the performance file can be cumbersome, and sometimes performance data is insufficient to cover all of the performance map quantities, as is genenrally the case with manufacturer data. Fortunately, there is a preprocessing tool available to remedy both of those problems.
Performance maps are represented as multidimensional arrays, each dimension corresponding to a certain input quantity and having a certain number of entries. The performance maps input quantities must include
the room dry-bulb temperature,
the outdoor dry-bulb temperature,
the normalized indoor volumetric air flow rate,
the normalized compressor frequency.
Cooling performance maps must also include the room wet-bulb temperature, to determine the sensible and latent capacity fractions. This means that heating performance maps have four dimensions, while cooling performance maps have five. Regarding the outputs, heating performance maps must provide values for the total input power and the total heating capacity. Cooling performance maps must also provide the total input power, along with the sensible and latent capacities.
Below are two examples of performance files, one for cooling and one for heating mode. Because there are many dimensions involved, performance files are ususally quite long, so only the first few lines are shown. The performance file begins by providing the dimensions of the performance map, along with the operating range associated with each input quantity. Then, it specifies the entries along each dimension, and finally the output values for every combination of the specified entries. Note that the input quantities must always be specified in the same order (room dry-bulb temperature first, then room wet-bulb temperature in cooling mode, then outdoor temperature, etc.). The firsts columns contain the entries combinations of each input quantity, with the rightmost quantity (the frequency) varying first. This ensures that the outut values are provided in the right order.
1!# This is a data file for Type 3254. Do not change the format.
2!# In PARTICULAR, LINES STARTING WITH !# MUST BE LEFT IN THE FILE AT THEIR LOCATION.
3!# Comments within "normal lines" (not starting with !#) are optional but the data must be there.
4!#
5!# Independent variables
6!#
7!# Number of Tdbr data points, lower bound, upper bound
8 6 17.8 32.2
9!# Number of Twbr data points, lower bound, upper bound
10 6 12.2 22.8
11!# Number of Tdbo data points, lower bound, upper bound
12 12 -10.0 46.0
13!# Number of AFR data points, lower bound, upper bound
14 2 1e-05 1.0
15!# Number of freq data points, lower bound, upper bound
16 14 0 1.4
17!# Tdbr values
18 17.8 21.1 23.9 26.7 29.4 32.2
19!# Twbr values
20 12.2 15.6 17.2 19.4 21.7 22.8
21!# Tdbo values
22 -10.0 -5.0 0.0 5.0 10.0 15.0 19.4 25.0 30.6 35.0 40.0 46.0
23!# AFR values
24 1e-05 1.0
25!# freq values
26 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4
27!#
28!# Performance map
29!#
30!# Tdbr Twbr Tdbo AFR freq power sensible_capacity latent_capacity
31 17.8 12.2 -10.0 1e-05 0.1 0.0032678034 0.0078270881 0.0095924383
32 17.8 12.2 -10.0 1e-05 0.2 0.015247431 0.0365067728 0.0447406448
33 17.8 12.2 -10.0 1e-05 0.3 0.0370154551 0.0862034025 0.1056460355
34 17.8 12.2 -10.0 1e-05 0.4 0.0683302257 0.148510872 0.1820065612
35 17.8 12.2 -10.0 1e-05 0.5 0.1080097759 0.211626558 0.2593575915
36 17.8 12.2 -10.0 1e-05 0.6 0.1541484803 0.2658985541 0.3258702935
37 17.8 12.2 -10.0 1e-05 0.7 0.2043652562 0.3075138351 0.3768716382
38 17.8 12.2 -10.0 1e-05 0.8 0.2560852354 0.3384178314 0.4147458357
39 17.8 12.2 -10.0 1e-05 0.9 0.3068232438 0.363399964 0.4453625305
40 17.8 12.2 -10.0 1e-05 1.0 0.3544303797 0.386779851 0.4740156035
41 17.8 12.2 -10.0 1e-05 1.1 0.3972710888 0.4105953643 0.5032025554
42 17.8 12.2 -10.0 1e-05 1.2 0.4343122105 0.4346359002 0.5326652823
43 17.8 12.2 -10.0 1e-05 1.3 0.4651227291 0.4575091829 0.5606974894
44 17.8 12.2 -10.0 1e-05 1.4 0.4897987153 0.4777544533 0.5855089526
45 17.8 12.2 -10.0 1.0 0.1 0.0032678034 0.0078270881 0.0095924383
46 17.8 12.2 -10.0 1.0 0.2 0.015247431 0.0365067728 0.0447406448
47 17.8 12.2 -10.0 1.0 0.3 0.0370154551 0.0862034025 0.1056460355
48 17.8 12.2 -10.0 1.0 0.4 0.0683302257 0.148510872 0.1820065612
49 17.8 12.2 -10.0 1.0 0.5 0.1080097759 0.211626558 0.2593575915
50 17.8 12.2 -10.0 1.0 0.6 0.1541484803 0.2658985541 0.3258702935
51 17.8 12.2 -10.0 1.0 0.7 0.2043652562 0.3075138351 0.3768716382
52 17.8 12.2 -10.0 1.0 0.8 0.2560852354 0.3384178314 0.4147458357
53 17.8 12.2 -10.0 1.0 0.9 0.3068232438 0.363399964 0.4453625305
54 17.8 12.2 -10.0 1.0 1.0 0.3544303797 0.386779851 0.4740156035
55 17.8 12.2 -10.0 1.0 1.1 0.3972710888 0.4105953643 0.5032025554
56 17.8 12.2 -10.0 1.0 1.2 0.4343122105 0.4346359002 0.5326652823
57 17.8 12.2 -10.0 1.0 1.3 0.4651227291 0.4575091829 0.5606974894
58 17.8 12.2 -10.0 1.0 1.4 0.4897987153 0.4777544533 0.5855089526
59 17.8 12.2 -5.0 1e-05 0.1 0.0038513398 0.0077754241 0.0095291219
60 17.8 12.2 -5.0 1e-05 0.2 0.0179701865 0.036265804 0.044445327
1!# This is a data file for Type 3254. Do not change the format.
2!# In PARTICULAR, LINES STARTING WITH !# MUST BE LEFT IN THE FILE AT THEIR LOCATION.
3!# Comments within "normal lines" (not starting with !#) are optional but the data must be there.
4!#
5!# Independent variables
6!#
7!# Number of Tdbr data points, lower bound, upper bound
8 4 15.6 23.9
9!# Number of Tdbo data points, lower bound, upper bound
10 10 -26.1 15.0
11!# Number of AFR data points, lower bound, upper bound
12 2 1e-05 1.0
13!# Number of freq data points, lower bound, upper bound
14 20 0 2
15!# Tdbr values
16 15.6 18.3 21.1 23.9
17!# Tdbo values
18 -26.1 -20.6 -15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0
19!# AFR values
20 1e-05 1.0
21!# freq values
22 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
23!#
24!# Performance map
25!#
26!# Tdbr Tdbo AFR freq power capacity
27 15.6 -26.1 1e-05 0.1 0.003178591 0.0025479775
28 15.6 -26.1 1e-05 0.2 0.0186176684 0.0149240341
29 15.6 -26.1 1e-05 0.3 0.0520713887 0.0417407361
30 15.6 -26.1 1e-05 0.4 0.1072392615 0.0859636323
31 15.6 -26.1 1e-05 0.5 0.1861736662 0.1492379224
32 15.6 -26.1 1e-05 0.6 0.2892808725 0.2305285764
33 15.6 -26.1 1e-05 0.7 0.4153039359 0.3189541754
34 15.6 -26.1 1e-05 0.8 0.5613908536 0.4028984669
35 15.6 -26.1 1e-05 0.9 0.723289038 0.4733228775
36 15.6 -26.1 1e-05 1.0 0.8956723774 0.5262791482
37 15.6 -26.1 1e-05 1.1 1.0725789877 0.5634360902
38 15.6 -26.1 1e-05 1.2 1.2479148976 0.5901976742
39 15.6 -26.1 1e-05 1.3 1.4159640763 0.612731807
40 15.6 -26.1 1e-05 1.4 1.5718411744 0.6355189604
41 15.6 -26.1 1e-05 1.5 1.7118311746 0.6603478707
42 15.6 -26.1 1e-05 1.6 1.833578394 0.6867006008
43 15.6 -26.1 1e-05 1.7 1.9361121244 0.7128479986
44 15.6 -26.1 1e-05 1.8 2.0197222658 0.7369319946
45 15.6 -26.1 1e-05 1.9 2.0857201122 0.757631318
46 15.6 -26.1 1e-05 2.0 2.1361327416 0.7743642738
47 15.6 -26.1 1.0 0.1 0.003178591 0.0025479775
48 15.6 -26.1 1.0 0.2 0.0186176684 0.0149240341
49 15.6 -26.1 1.0 0.3 0.0520713887 0.0417407361
50 15.6 -26.1 1.0 0.4 0.1072392615 0.0859636323
51 15.6 -26.1 1.0 0.5 0.1861736662 0.1492379224
52 15.6 -26.1 1.0 0.6 0.2892808725 0.2305285764
53 15.6 -26.1 1.0 0.7 0.4153039359 0.3189541754
54 15.6 -26.1 1.0 0.8 0.5613908536 0.4028984669
55 15.6 -26.1 1.0 0.9 0.723289038 0.4733228775
56 15.6 -26.1 1.0 1.0 0.8956723774 0.5262791482
57 15.6 -26.1 1.0 1.1 1.0725789877 0.5634360902
58 15.6 -26.1 1.0 1.2 1.2479148976 0.5901976742
59 15.6 -26.1 1.0 1.3 1.4159640763 0.612731807
60 15.6 -26.1 1.0 1.4 1.5718411744 0.6355189604